Free Voltage Drop Calculator

Check voltage drop on a run before you pull wire. Enter the system, conductor, wire size, load and length to see the drop in volts and percent, and the voltage at the load.

How to use the voltage drop calculator

  1. Pick single-phase or three-phase and enter the voltage (240 by default).
  2. Pick copper or aluminum conductors.
  3. Pick the wire size in AWG (10 by default).
  4. Enter the load current (30 A) and the one-way length of the run (100 ft).
  5. Read the voltage drop, the percent drop and the voltage at the load.

How the calculation works

The calculator uses the common K-factor formula. K is the resistance constant of the conductor: 12.9 for copper and 21.2 for aluminum. CM is the wire's area in circular mils, which the calculator looks up from the AWG size you pick, from 14 AWG (4,110 cmil) up to 4/0 (211,600 cmil).

For single-phase, voltage drop = 2 × K × amps × one-way length ÷ CM. For three-phase, it's 1.732 × K × amps × length ÷ CM. Use the one-way length, from the panel to the load.

The percent drop is the voltage drop ÷ the system voltage. The voltage at the load is the system voltage minus the drop.

If the drop is above 3%, the calculator flags it. That follows the common NEC informational-note recommendation: 3% for a branch circuit and 5% total for feeder plus branch circuit. A larger wire size lowers the drop.

This is a quick check, not a substitute for code compliance or an engineer. Local code and the inspector have the final say. Everything runs in your browser.

Example: 30 A on 10 AWG copper, 100 ft

Using the defaults: single-phase, 240 V, copper (K = 12.9), 10 AWG (10,380 cmil), 30 A and a 100-foot one-way run.

Voltage drop = 2 × 12.9 × 30 × 100 ÷ 10,380 = 7.46 V. That's 3.11% of 240 V, so the voltage at the load is about 232.5 V.

Because 3.11% is above 3%, the calculator flags it. Try 8 AWG (16,510 cmil) with the same inputs and the drop comes down, since a bigger wire has less resistance per foot.

Three-phase systems use 1.732 instead of 2 in the formula, so the same wire, load and length gives a smaller drop. Switch the system to three-phase with the defaults and the calculator does the math for you.

Aluminum works the other way. Switch the conductor to aluminum and K goes from 12.9 to 21.2, so the drop on the same 10 AWG run is higher. That's why aluminum feeders are usually sized up compared with copper.

5 tips for keeping voltage drop down

Things to check on long runs:

  • Measure the one-way length from the panel to the load, not the round trip.
  • Upsize the wire when a long run flags above 3%.
  • Remember aluminum has a higher K, so it needs a larger size than copper for the same drop.
  • Use the actual load current, not just the breaker size, when you know it.
  • Confirm the final wire size meets code for ampacity, not just voltage drop.

Why voltage drop matters

Every wire has some resistance. The longer the run and the higher the current, the more voltage is lost along the way. The equipment at the end of the run gets less than the panel supplies.

Too much drop can make motors run hotter and work harder, make lights dim, and cause sensitive equipment to act up. It also means some of the power you pay for is turned into heat in the wire.

Long runs are where this shows up most: detached garages, shops, well pumps, outdoor lighting, EV chargers and subpanels at the far end of a building. On those jobs, it's worth checking the drop before you choose a wire size, not after the wire is in the wall.

The fix is usually a bigger wire. Each step up in AWG adds circular mils, which lowers the drop. Run the numbers at a couple of sizes, then pick the one that meets both the drop you want and the ampacity the circuit needs under code.

See video ad ideas for plumbing and electrical businesses →

FAQ

Questions about this tool

How do you calculate voltage drop?
For single-phase, voltage drop = 2 × K × amps × one-way length ÷ circular mils. For three-phase, replace 2 with 1.732. K is 12.9 for copper and 21.2 for aluminum. With the defaults, 2 × 12.9 × 30 × 100 ÷ 10,380 = 7.46 V.
What is the acceptable voltage drop?
A common NEC informational-note recommendation is 3% for a branch circuit and 5% total for the feeder and branch circuit together. The calculator flags anything above 3%. It's a recommendation, so check your local code and what your inspector expects.
Should I use one-way or round-trip length?
Enter the one-way length, from the panel to the load. The single-phase formula already multiplies by 2 to account for the current going out and coming back. The three-phase formula uses 1.732 instead. If you enter the round-trip length, the result will be twice as high as it should be.
Why does aluminum have more voltage drop than copper?
Aluminum has higher resistance than copper for the same size wire. The calculator uses K = 21.2 for aluminum and 12.9 for copper. That's why aluminum runs often need a larger wire size to keep the drop under the same percent.
Can this calculator replace a code check?
No. It's a quick estimate of voltage drop only. Wire sizing also depends on ampacity, temperature ratings, conduit fill and local code. It's not a substitute for code compliance or an engineer, so confirm your design with the rules that apply to your job.
Get your video

Win more electrical jobs with a $50 video ad

Tell us a little about your business. We'll write the script and send your preview, and you pay nothing until you approve it.

  • No payment now. Not even a card.
  • A real person replies, usually within a few hours.
  • Unlimited revisions until it's right.

Prefer email? Write to info@blazevideos.com

Video length

No payment needed. We'll reply by email.

Get my $50 video, pay after